Upgrading your service will not keep individual circuits from tripping.
An overloaded circuit on a 400-amp service will still trip.
Large individual loads require their own circuit.
Large circuits with multiple outlets and numerous simultaneous loads should be broken up into multiple circuits as suit the loads.
The only time it is necessary to increase a service from 100 amps to 200 amps is when the combined loads dictate the necessity.
A 100-amp service is usually adequate for a three or four bedroom home with electric hot water, electric stove and electric dryer.
A 200-amp service would be necessary if total electric heat is contemplated. <><><>
As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.
If you do this work yourself, always turn off the power
at the breaker box/fuse panel BEFORE you attempt to do any work AND
always use an electrician's test meter having metal-tipped probes
(not a simple proximity voltage indicator)
to insure the circuit is, in fact, de-energized.
IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB
SAFELY AND COMPETENTLY
REFER THIS WORK TO QUALIFIED PROFESSIONALS.
Look at the value of the breaker or fuses that control your main electric panel.
look at the wire size coming in to the main lugs on service panel, I am assuming you don't have a main breaker or you would look at the breaker rating to determine service size. 2/0 copper or 4/0 aluminum service size 200 amps, #4 copper or # 2 aluminum 100 amp.
No, each size service needs its own meter base.
Yes, but at every reduction in wire size there has to be a breaker sized to the smaller wire size. The wire size for 100 amp panels is recommended at #3 copper conductor. From the 200 amp feeder panel you will require a 100 amp two pole breaker for each of the two 100 amp services. Keep in mind that if you run the 100 amp services close to maximum this will take away the capacity of the 200 amp service for other branch circuits coming off of it. Also keep in mind that if the panels are located, not in the same building as the 200 amp service that the 100 amp panels will be treated as separate services and will have to be constructed like a 100 amp service. This includes ground rods. Also the bonding screw will have to be removed that connects the neutral buss to the panel enclosure.
In a 200 amp service, each leg carries 100 amps. However, since the legs are 180 degrees out of phase, you can achieve 240 volts across both legs. So, a 200 amp service typically consists of two 120 volt legs, each providing up to 100 amps.
The number of circuits you can have on a 200 amp service depends on the load of each circuit. As a general rule of thumb, you can have up to 40-50 circuits on a 200 amp service panel, but this can vary based on the specific requirements of your electrical system and local codes. It's important to consult with a licensed electrician to determine the appropriate number of circuits for your installation.
No, it is not safe or recommended to connect a 200 amp service to a 125 amp panel. The panel must be rated to match the amperage of the service to avoid overloading the panel and potential fire hazards. It is important to upgrade the panel to match the service amperage.
No, each size service needs its own meter base.
Yes, but at every reduction in wire size there has to be a breaker sized to the smaller wire size. The wire size for 100 amp panels is recommended at #3 copper conductor. From the 200 amp feeder panel you will require a 100 amp two pole breaker for each of the two 100 amp services. Keep in mind that if you run the 100 amp services close to maximum this will take away the capacity of the 200 amp service for other branch circuits coming off of it. Also keep in mind that if the panels are located, not in the same building as the 200 amp service that the 100 amp panels will be treated as separate services and will have to be constructed like a 100 amp service. This includes ground rods. Also the bonding screw will have to be removed that connects the neutral buss to the panel enclosure.
Yes, the wire size has to be increased. The existing 100 amp service will now probably have a #3 conductor with an insulation factor of 75 or 90 degrees C which is rated for 100 and 105 amps respectively. Increasing to a 150 amp service will use a #1/0 wire size. If you are thinking of an upgrade, skip the 150 amp service and go to a 200 amp panel. New homes are installing 200 amp 42 circuit panels. The extra cost is only reflected in the materials as the labour costs will be the same regardless whether a 150 amp or a 200 amp panel is installed. The wire size for a 200 amp panel is #3/0. With an insulation factor of 75 or 90 degrees C the rating is 200 or 210 amps respectively.
Depends on the size of the service. 100 amp service will require 3 gauge, 150 amp service will require 1/0 gauge, and 200 amp service will require 3/0 gauge.
In a 200 amp service, each leg carries 100 amps. However, since the legs are 180 degrees out of phase, you can achieve 240 volts across both legs. So, a 200 amp service typically consists of two 120 volt legs, each providing up to 100 amps.
Yes you can as long as the sensing coils of the transfer switch are the same as the 100 amp service. The transfer switch has to be able to tell when the voltage is back from the utility side of the switch when the power is restored.
The number of circuits you can have on a 200 amp service depends on the load of each circuit. As a general rule of thumb, you can have up to 40-50 circuits on a 200 amp service panel, but this can vary based on the specific requirements of your electrical system and local codes. It's important to consult with a licensed electrician to determine the appropriate number of circuits for your installation.
Check the nameplate on the service panel. There it will tell you what the buss capacity is. On a 200 amp service nothing in the wiring configuration is allowed to be less than that the service rating. In the market there are 200 amp 42 circuit distribution panels.
sounds like you have a 100 amp service to your home.. that will need to be upgraded to a 200 amp service.. you shouldn't have any problems after upgrade..
A #6 copper conductor is used to bond a 200 amp distribution.
No, it is not safe or recommended to connect a 200 amp service to a 125 amp panel. The panel must be rated to match the amperage of the service to avoid overloading the panel and potential fire hazards. It is important to upgrade the panel to match the service amperage.
This is a voltage drop question. A voltage must be stated to answer this question.