For single phase, KVA = (line to ground) * (phase current).

A 75kVA 480 to 208Y/120 volt transformer is a fairly common transformer. I assume this is the type of transformer you are referring to. 75k / 120 = 625 Amps.

As an FYI, the 208Y voltage is the line to line voltage, which is equal to (phase 1) - (phase 2), where the phases are separated by 120 degrees, thus (phase 1) * 1.732

For three phase, kVA = (line to line voltage) * (phase current) *(sqrt 3),

75k / 208 / 1.732 = 208 Amps.

User Avatar

Wiki User

14y ago
This answer is:
User Avatar
More answers
User Avatar

Wiki User

13y ago

A 150kVA transformer, stepdown from 4160V to 600V, 3 phase, will have 20.8A on the primary side and 144.3A on the secondary side assuming the TX is 100% efficient, they are usually 2-3% losses to noise and heat etc.

This answer is:
User Avatar

User Avatar

Wiki User

11y ago

To answer this question a voltage must be stated. I = KVA x 1000/1.73 x E. Amps = KVA x 1000/1.73 x Volts.

This answer is:
User Avatar

User Avatar

Wiki User

12y ago

The formula you are looking for is Amps = kva x 1000/1.73 x Volts.

This answer is:
User Avatar

User Avatar

Wiki User

12y ago

15 kva is 15,000 volt-amps, that means the volts times the amps equals 15,000, so the amps are 15,000 / 220, or 68 amps.

This answer is:
User Avatar

User Avatar

Wiki User

15y ago

The formula you are looking for is Amps = kva x 1000/1.73 x voltage = 18 amps

This answer is:
User Avatar

User Avatar

Wiki User

12y ago

yep

This answer is:
User Avatar

User Avatar

Anonymous

Lvl 1
4y ago

Divid 17500 wraps by 585 wraps

75 kV divided by 30= 2.5

This answer is:
User Avatar

User Avatar

Anonymous

Lvl 1
3y ago

200 amps

This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: How many output amps is a 75 kva transformer?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

Can you use a step up transformer 110220 with output of 16 kva?

Yes, but your input current is going to be high at 133 amps. The output of the transformer is not going to be 16 KVA, that is the rating of the transformer.


How much actual power does a 1KA transformer provide?

The kVA represents the power-handling capability of the transformer.So, if you were using a 1 kVA transformer at 110 volts, you could roughly estimate the maximum output to be 9 amps.


How many amps will a 250 kVA transformer in 220 volts secondary?

kVA = 1000va Therefore 1000/220 Answer 4.54A


How do you calculate the output voltage of a transformer if kva rating is known?

You can't determine the output voltage of a transformer by knowing kva. Transformers will be marked as to input and output voltages. Some will have multiple input and output voltages. The output voltage depends on the ratio of coil turns between input and output.


How many amps will a 37.5 KVA transformer carry?

It depends on the rated voltage of its secondary.


How many output amps from a 75kva transformer fed with 480 ckt.?

It depends on what the output voltage is. You only specified the input voltage, not the output voltage. The equation is 75 Kva = {some} amps times {some} kilovolts. (Minus incidental losses, of course, but you still need to know output volts.)


How many output amps is a 45 kva transformer?

There is not enough information provided to answer. KVA is short for "Kilo Volt Amperes". That is, thousands of Volt Amps. In order to determine how many Amperes are flowing, you must know at what voltage it is operating. Amperes = 45,000 ÷ volts Bill Slugg


How many amps on 25 kva transformer 1phase secondary 230 volts?

Take the KVA and divide it by the voltage. 25/.230 = 109 amps. The transformer can put out up to 50% more that its rated for short durations. So you could get around 150 amps out of a 25 Kva tranformer in a worst case situation.


How many output amps is a 75 KVA generator single phase?

The formula you are looking for is , A = kva x 1000/Volts.


What size ground wire for a 30 kva transformer?

The size of grounding wire is based on the amperage output of the transformer. The voltage of the transformer needs to be stated. Without this voltage a calculation can not be made. Amps = Watts/Volts = 30000/?.


How many amps will a 10 kva transformer handle?

It depends on how many amps it was designed for. A 12.5kV/600v 10kVA 3 phase transformer can handle ~.5 amps on the primary and ~10A on the secondary. A 600/120V 10kVA 3 phase transformer can handle ~10A on the primary and ~50 on the secondary.


How are transformer rated?

kva k-kilo v-voltage a-amps(current)