In a three phase 225 amp panel, there would be a total of 225 amps available for each phase, making it a total of 675 amps for all three phases combined. This means that you could have up to 225 amps of current flowing through each phase simultaneously.
On a 50 amp 3 phase connector, you can pull 50 amps per leg. This means that each of the three phases can carry up to 50 amps individually, resulting in a total capacity of 50 amps per leg.
To calculate the current draw, use the formula: Current (A) = Power (W) / (Voltage (V) * √3). Plugging in the values, we get Current = 30000W / (208V * √3) ≈ 78.7A. So, a 30KW strip heater operating at 208 volts 3-phase would draw approximately 78.7 amps.
The equation that you are looking for is Amps = Watts/Volts. There are 6000 watts in 6kW.
To convert from kilowatts (kW) to amps in a 3-phase system, you can use the formula: Amps = (kW × 1000) / (√3 × volts). In this case, with 42 kW and a voltage of 120208 V, the amperage would be around 139 amps.
In a three phase 225 amp panel, there would be a total of 225 amps available for each phase, making it a total of 675 amps for all three phases combined. This means that you could have up to 225 amps of current flowing through each phase simultaneously.
For a single phase circuit, the equation you are looking for is I = W/E. Amps = Watts/Volts.
50 Amps Single Phase 20 Amps Three Phase
106 amps
On a 50 amp 3 phase connector, you can pull 50 amps per leg. This means that each of the three phases can carry up to 50 amps individually, resulting in a total capacity of 50 amps per leg.
9
To answer this question the voltage of the generator must be given.
62.5 amps
At 240v single phase it's 70.8 amps. If it runs on 2 wires plus ground, take the voltage rating of the equipment and divide that into the watts to get amps. At 480v 3 phase it's 25.8 amps. At 208v 3 phase it's 47.2 amps. <<>> There are zero amps in 14 kW. A voltage needs to be stated. I = W/E, Amps = Watts/Volts.
UK Mains is 230V therefore 6 KW is 6000/230 = 26 Amps. 3 phase is slightly different....... 6000/400V = 15 Amps/root 3 = 8.67 Amps per phase.
To calculate the current draw, use the formula: Current (A) = Power (W) / (Voltage (V) * √3). Plugging in the values, we get Current = 30000W / (208V * √3) ≈ 78.7A. So, a 30KW strip heater operating at 208 volts 3-phase would draw approximately 78.7 amps.
UK Mains is 230V therefore 6 KW is 6000/230 = 26 Amps. 3 phase is slightly different....... 6000/400V = 15 Amps/root 3 = 8.67 Amps per phase.