On a 240 v supply the heater takes 22.5 amps so a 30-amp breaker is OK. On different voltages the current would be different.
Look on the heater and see what amps it is pulling. That will determine the wire size and breaker size. It must be on a dedicated circuit. 15 amps = AWG # 14 wire with 15 amp breaker 20 amps = AWG # 12 wire with 20 amp breaker 30 amps = AWG # 10 wire with 30 amp breaker 40 amps = AWG # 8 wire with 40 amp breaker
The formula you are looking for is I = W/E, Amps = Watts/Volts. Amps = 5000/230 =21.7 amps. The wire size to run this heater would be a #10 copper conductor. The supply breaker would be a two pole 30 amp breaker.
What size breakers are needed for a 30kva transformer 208 volt feed 600 volt out put
A 400 watt heater can safely be used on a 15 amp circuit. The size breaker needed for a circuit is determined by the size of the wiring in that circuit. AWG #14 wire requires a 15 amp breaker. AWG # 12 wire requires a 20 amp breaker.
I = W/E. 1500/240 = 6 amps for each heater. In parallel the total connected load will be 12 amps. A #14 conductor is rated at 15 amps and de rated to 80% can carry 12 amps continuous. The breaker needed for this would be a two pole 15 amp breaker. If this is a new installation I would use a #12 conductor for the two heaters on a two pole 20 amp breaker. The conductors will run much cooler using a larger size.
To answer this question the voltage of the immersion heater is needed. I = W/E.
Look on the heater and see what amps it is pulling. That will determine the wire size and breaker size. It must be on a dedicated circuit. 15 amps = AWG # 14 wire with 15 amp breaker 20 amps = AWG # 12 wire with 20 amp breaker 30 amps = AWG # 10 wire with 30 amp breaker 40 amps = AWG # 8 wire with 40 amp breaker
The formula you are looking for is I = W/E, Amps = Watts/Volts. Amps = 5000/230 =21.7 amps. The wire size to run this heater would be a #10 copper conductor. The supply breaker would be a two pole 30 amp breaker.
What size breakers are needed for a 30kva transformer 208 volt feed 600 volt out put
A 400 watt heater can safely be used on a 15 amp circuit. The size breaker needed for a circuit is determined by the size of the wiring in that circuit. AWG #14 wire requires a 15 amp breaker. AWG # 12 wire requires a 20 amp breaker.
I = W/E. 1500/240 = 6 amps for each heater. In parallel the total connected load will be 12 amps. A #14 conductor is rated at 15 amps and de rated to 80% can carry 12 amps continuous. The breaker needed for this would be a two pole 15 amp breaker. If this is a new installation I would use a #12 conductor for the two heaters on a two pole 20 amp breaker. The conductors will run much cooler using a larger size.
Each baseboard heater will draw a little over 4 amps at 120 volts or 2 Amps at 240 volts. The total number of baseboards on a circuit will draw the sum of these amps. Keep the load under 80% of the amperage rating of the breaker.
A double breaker is a breaker that has 2 switches on it. One of the switches is 20 amps and the other is 30 amps.
A 2000 watt heater draws 8.3 amps on a 240 v supply, so the cutout should be set to 10 or 12 amps. <<>> In North America a 2000 watt baseboard heater will be fed with a two pole 15 amp breaker. A two wire cable of #14 copper will be used to connect the supply voltage to the heater.
Yes, the total amperage load of a 2000 watt heater at 240 volts is 8.3 amps. Keep in mind that the wire feeding the heater must be a #10 because the breaker is rated at 25 amps. A wire's ampacity rating can be larger that the breaker amperage rating but never smaller. Example, a #14 rated at 15 amps or a #12 rated at 20 amps can not be connected to a 25 amp breaker. The 25 amp breaker does not trip until it reaches 25 amps well over the allowable amperage of the #14 amd #12 wire. This is why a #10 wire must be used as its rating is 30 amps.
Current in amps = watts/ voltage in volts. If you have a 240 volt supply, it will draw 4800/240 = 20 amps, so no. This is a very powerful water heater, and would normally be wired into a dedicated circuit, presumably with a 30 amp breaker.
Canada and US - Standard size breaker in home panel is 40 amps for stove. If not standard range open Discuss Question page.