answersLogoWhite

0

Yes the voltage rating of devices is the maximum amount of voltage that it can handle. You could not use a 480 volt breaker on a 600 volt service and like wise you could not use a 208 volt rated breaker on a 480 volt service.

User Avatar

Wiki User

16y ago

What else can I help you with?

Continue Learning about Natural Sciences

What is the primary feed for a 480v to 208v 100amp panel 3phase?

The primary feed for a 480V to 208V, 100 amp panel in a three-phase system typically consists of three phases (L1, L2, L3) and a neutral wire, coming from a step-down transformer designed to convert the higher voltage to the lower voltage. The transformer will have a primary side connected to the 480V supply and a secondary side that outputs 208V. Additionally, proper grounding must be ensured for safety and compliance with electrical codes. The panel will distribute the 208V power to various circuits as needed.


What size main breaker feeding 480v 75 kva transformer?

An exact breaker size can not be given because the voltage, and hence the calculation for current, is not given. A transformer shall be protected by an over current device that is not rated at more that 150% of the primary current.


Can you connect a 240V ballast to 208V line service?

It is not recommended to connect a 240V ballast to a 208V line service as this can potentially damage the ballast and create a safety hazard. It is best to use a ballast that is specifically designed for use with a 208V line service to ensure safe and proper operation.


How big of breaker do you use for 115 volt?

Depends on the wire size used in the circuit. If you use AWG # 14 wire you must use a 15 amp breaker. If it is wired with AWG # 12 wire then you use a 20 amp breaker. If a AWG # 10 wire is used then a 30 amp breaker is required. The breaker protects the wiring from overheating so you must use the proper size breaker for the wire used.


How do we know when to connect to 208v or 240v?

Its on the specifications of the device you will plug

Related Questions

Can you feed a 208v 200amp panel from 480v 20amp circuit?

Not directly, you would need to transform 480v circuit to 120v with a transformer first.


What is the primary feed for a 480v to 208v 100amp panel 3phase?

The primary feed for a 480V to 208V, 100 amp panel in a three-phase system typically consists of three phases (L1, L2, L3) and a neutral wire, coming from a step-down transformer designed to convert the higher voltage to the lower voltage. The transformer will have a primary side connected to the 480V supply and a secondary side that outputs 208V. Additionally, proper grounding must be ensured for safety and compliance with electrical codes. The panel will distribute the 208V power to various circuits as needed.


What is the kw input on a 50amp breaker with a 208v three phase electrical feed?

7200


What size main breaker feeding 480v 75 kva transformer?

An exact breaker size can not be given because the voltage, and hence the calculation for current, is not given. A transformer shall be protected by an over current device that is not rated at more that 150% of the primary current.


What is low voltage transmission?

In the supply industry it refers to circuits of below 1000 volts. Common voltages used are 120v, 208v, 230v, 240v, 277v, 400v, 415v, 480v.


Is there any advantage of 208V vs 480V three phase?

208 v. equipment is a little smaller and cheaper, and 208v. is slightly safer to use. However, 480v. runs on half the amperage 208v. equipment does, which means equipment or devices cost almost 50% less to operate. With respect to energy consumption, the answer above is incorrect. It is true that equipment that operates at 480v does operate at roughly half the amperage vs. 208v, however, it operates at over twice the voltage. Your local power company charges you per kilowatt hour (voltage x amperage), not on amperage alone. Example, a 208v motor that draws 10 amps would consume (208v x 10a) 2.080 kilowatts per hour. The same motor on 480v would draw roughly half, 4.3 amps (480v x 4.3a) and would also consume 2.080 kilowatts per hour. So in terms of power consumption, they are virtually the same. The main reasons one would opt for higher is the fact that you can install smaller wire and you can run longer distances. It's a ratio that is directly proportional (at least with electric motors/inductive loads). If you were comparing a 240v motor to a 480v motor the ratio would be exact, if a 480v motor draws 5 amps, the same motor on 240v would draw 10 amps.


What rating is called for in a non fussed disconnect switch between a Automatic Transfer Switch with a 400amp breaker 120 208v system and a generator that outputs 120 208v 3ph capacity 100KW 125KVA?

400 amps


Are 120V and 208V the same?

no 208v is bigger


Can you connect a 240V ballast to 208V line service?

It is not recommended to connect a 240V ballast to a 208V line service as this can potentially damage the ballast and create a safety hazard. It is best to use a ballast that is specifically designed for use with a 208V line service to ensure safe and proper operation.


Can a 600V rated cable be use in 480V 3 Phase Ckt?

yes,


How many output amps is a 75 kva 208v-480v?

1kw=1.25kvaby this relation 75kva=60kwp=1.732*380*I*1I=60000/1.732*380*1I=91AmpsCommentPower factor is irrelevant to this question. You don't need to convert the kV.A rating to kilowatts, simply divide 75 000 V.A by (1.732 x 380). The answer is 114 A.This, of course, assumes that the question refers to a three-phase generator and that 380 V is the line voltage.


How many output amps is a 45 kva transformer?

There is not enough information provided to answer. KVA is short for "Kilo Volt Amperes". That is, thousands of Volt Amps. In order to determine how many Amperes are flowing, you must know at what voltage it is operating. Amperes = 45,000 ÷ volts Bill Slugg