answersLogoWhite

0

This vector group test is done to confirm whether the vector group provided in the name plate is correct or not and also to confirm that the winding has not been damaged during transport, installation and erection.

Taking a particular example, for Dyn11 transformer we have to apply 3~ 400v to the primary, with primary 'U' & secondary 'u' shorted....

then check the voltage across different terminals such as V-v, V-w, W-w, W-v

for Dyn11 configuration (V-v = V-w = W-w)less than W-v....

you can compare the results after drawing the vector diagram for the same......

the purpose of shorting the primary U & secondary u is to nullify the phase shift, to obtain a reference vector...

User Avatar

Wiki User

9y ago

What else can I help you with?

Continue Learning about Engineering

Using vector to add objects and display their member variables?

import java.util.Vector; suppose-:::: test t=new test(); /**this is how we add elements to vector*/ Vector v=new Vector(); v.addElements(t);


Why the open and short ckt test of transformer is needed?

The open/short-circuit test on a transformer isn't 'needed'. It's only used if you want to find out the efficiency of a transformer.


What is the use of back to back test in transformer?

Back to back test give data for finding the regulation , efficiency and heating under load condition. Back to back test is performed in the presence of two identical transformer. In this test one transformer remains open and other remains loaded. Hence sumpner's back to back test is generalised form of o/c test and s/c test which is performed within one test only. Hence from this test we find core loss and full load copper loss simultaneously at a time.


Can a high voltage transformer be megged with a megger meter?

No. A megger's output voltage is not high enough to test the insulation of a high-voltage transformer if, by 'high-voltage transformer ', you mean a distribution transformer or power transformer. Instead, a high-voltage test set or 'pressure tester' (e.g. a 'HiPot' tester) must be used, as these produce far higher voltages.


What types of transformer tests are there?

there are various types of trasformer tests are here Open Ckt test Short ckt test IR value test Vector group test Phase sequence test Magnetizing test turn ratio test T/f oil insulation breakdown test and so on............

Related Questions

How do you test Yyn0 vector group of transformer?

in electrical engineering


How can you test the vector group dyn5?

You can test a vector group DYn5 transformer by performing insulation resistance tests, turns ratio tests, winding resistance tests, and vector group verification tests using a suitable test set. It is recommended to follow the manufacturer's guidelines and relevant industry standards when conducting these tests.


What are precommissioning tests of transformers?

magnetising current test, magnetising balance test, s.c test, vector group test, winding resistance test, ratio test


What is dielectric test in transformer?

why need dielectric test for transformer


How will be conduct test on transformer?

Short circuit test and open circuit test are widely used to test the efficiency of the transformer.


What are the purposes of performing no load test for the transformer?

These two tests are performed on a transformer to determine (i) equivalent circuit of transformer(ii)voltage regulation of transformer(iii) efficiency of transformer. The power required for theseOpen Circuit test and Short Circuit test on transformeris equal to the power loss occurring in the transformer.


Using vector to add objects and display their member variables?

import java.util.Vector; suppose-:::: test t=new test(); /**this is how we add elements to vector*/ Vector v=new Vector(); v.addElements(t);


Why the open and short ckt test of transformer is needed?

The open/short-circuit test on a transformer isn't 'needed'. It's only used if you want to find out the efficiency of a transformer.


How can I test a doorbell transformer to ensure it is functioning properly?

To test a doorbell transformer, use a multimeter to measure the voltage output. Disconnect the transformer from the power source and test the voltage across the terminals. A properly functioning transformer should have a voltage output within the specified range.


Does vector marketing drug test?

no


How can I test a transformer on a furnace?

To test a transformer on a furnace, you can use a multimeter to check the voltage output. First, turn off the power to the furnace. Then, locate the transformer and measure the voltage across the primary and secondary terminals. If the voltage matches the specifications provided by the manufacturer, the transformer is functioning properly. If not, the transformer may need to be replaced.


What is circuit diagram for ratio test of transformer?

Mechanauts