Best Answer

Not necessarily. Reverse power simply means that the load is providing power to the generator, instead of the reverse. Its not a good place to be, because you waste the power needed to turn the generator, and you could damage it as well.

User Avatar

Wiki User

12y ago
This answer is:
User Avatar
More answers
User Avatar

Wiki User

11y ago

2 or more generators are run in parallel supplying power to the common bus. When one of them drag behind due to any reason, instead of delivering electric power to the bus, it takes power from the bus acting like a motor and trying to drive the engine, when it happens like this the circuit breaker trips immediately.

This answer is:
User Avatar

User Avatar

Wiki User

9y ago

The primary causes of reverse power on a generator are reverse rotation and incorrect wiring order. A generator is designed to operate in a single direction to produce electrical power.

This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What is reverse power in generator and what happens in couse of reverse power?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Engineering

What is a reverse KVAR relay?

The reverse KVAR relay protects a generator from a loss of excitation. When the excitation system is lost, reactive power will flow from the system back into the generator. When this happens, induced currents at twice the system frequency will flow in the rotor windings and rotor structure.


How reverse power will occur during synchronizing?

Reverse power flow into a generator can occur during synchronization if the generator is spinning too slowly, or the voltage phase angle is lagging relative to the power system. If the generator is spinning too slowly, power from the system is used by the generator to increase its' speed. If the phase angle is lagging, an initial spike of power will flow into the generator to force it into sync with the system. Typically generator's will match system frequency very closesly, and force the phase angle to leading slightly between the generator and the system. When synchronized, an extra bump of power will flow out while the generator is torqued into phase with the system. This will avoid tripping any reverse power devices.


What happens to power generated from a generator if not consumed?

The unused power goes to "waste"


What is the Operation of reverse power relay in a substation?

Reverse power relays are often used in generator protection to trip breakers if generators are "sucking in" power (since this shouldn't occur, it is a BAD thing when it does). I'm not sure there is a use for reverse power relays beyond this; directional relays looking in a reverse direction are often used in pilotting schemes, though (not "reverse power").


How control the reverspower for diesel generator?

I guess you're thinking that reverse power is a generation error, but it is a change in flow direction. When two generator are running in parallel nd of sudden a generator2 prime is dropped nd due to circuit breaker2 is still in on state Gen2 draws power from Gen1 and acts as a motor. this action will damage the prime mover(engine) nd AVR too. Of course upto 10 amp of reverse current is allowed into a generator as of considering as back emf (while running as generator). So in order to stop thing reverse power, a relay is used which senses the directional flow of power nd immediately turns off the circuit breaker of off prime mover unmatched droop also develops this reverse power flow because of change in voltage nd load sharing

Related questions

What is a reverse KVAR relay?

The reverse KVAR relay protects a generator from a loss of excitation. When the excitation system is lost, reactive power will flow from the system back into the generator. When this happens, induced currents at twice the system frequency will flow in the rotor windings and rotor structure.


How reverse power will occur during synchronizing?

Reverse power flow into a generator can occur during synchronization if the generator is spinning too slowly, or the voltage phase angle is lagging relative to the power system. If the generator is spinning too slowly, power from the system is used by the generator to increase its' speed. If the phase angle is lagging, an initial spike of power will flow into the generator to force it into sync with the system. Typically generator's will match system frequency very closesly, and force the phase angle to leading slightly between the generator and the system. When synchronized, an extra bump of power will flow out while the generator is torqued into phase with the system. This will avoid tripping any reverse power devices.


What happens to power generated from a generator if not consumed?

The unused power goes to "waste"


What is the Operation of reverse power relay in a substation?

Reverse power relays are often used in generator protection to trip breakers if generators are "sucking in" power (since this shouldn't occur, it is a BAD thing when it does). I'm not sure there is a use for reverse power relays beyond this; directional relays looking in a reverse direction are often used in pilotting schemes, though (not "reverse power").


How many times per second does the alternating current generated at large power generator reverse directions?

120


How control the reverspower for diesel generator?

I guess you're thinking that reverse power is a generation error, but it is a change in flow direction. When two generator are running in parallel nd of sudden a generator2 prime is dropped nd due to circuit breaker2 is still in on state Gen2 draws power from Gen1 and acts as a motor. this action will damage the prime mover(engine) nd AVR too. Of course upto 10 amp of reverse current is allowed into a generator as of considering as back emf (while running as generator). So in order to stop thing reverse power, a relay is used which senses the directional flow of power nd immediately turns off the circuit breaker of off prime mover unmatched droop also develops this reverse power flow because of change in voltage nd load sharing


What happens when you connect the synchronous generator to the grid at a different voltage from the grid?

if u connecting the synchronus generator to the grid at low voltage then it will act as a motor, reverse power will enter after some time winding is burn out if tripping is not occur at reverse power.


The kind of power produced when the energy of flowing water turns a generator turbine?

Hydroelectric power is made when this happens


What is reverse power of generator?

It is wise to start thinking of power in DC circuit. If a load is connected to a power source in a DC circuit, the corresponding VOLT CURRENT plot both will be in the positive quadrant. Of course, polarity must be correct. Now if the CURRENT (in the same polarity arrangement) happens to be in the negative quadrant, the power is said to be reversed. The same can be thought in an AC circuit. Taking a half wave cycle of both VOLT and CURRENT, one can apply the same understanding as in the DC circuit. If the AC circuit is capacitive or inductive, VOLT and CURRENT waves will be shifted according to the value of the capacitive or inductive load, and here one has to be aware. Adel Aljassar adel@al-jassar.net


Why does the synchroscope need to be rotating clockwise if it is turning slowly counterclockwise won't that work the same?

because the incoming generator has be connected as a source and not a load to the grid. if the frequency of the incoming generator is lower than the grid frequency then ... it will behave as a motor drawing power from the grid and generator will trip in reverse power protection.


Buy a Power Generator?

form_title=Buy a Power Generator form_header=Have a source of power in case of emergency or power outage. What type of power generator do you need?=_ What do you want to keep powered?=_ What is your budget for this power generator?=_


How do you test generator reverse power?

To test the generators reverse power relay to make sure the generator is spinning at the right speed and a fuel issue is not involved. If it is not a fuel issue you need to check the frequency of the electronic load and frequency. If both of these issues are okay check the diesel electronic control unit for dirt and dust. This unit needs to be clean.