What is mcm wire?

Updated: 10/31/2022
User Avatar

Wiki User

9y ago

Best Answer

MCM is another measure of wire gauge. It is somewhat confusing but it starts at around 40 gauge being the smallest wire up to the largest gauge of 1. from there you have oughts which is from 1 to 4 (1 ought, 2 ought etc) and then you have MCM which is circular mils. MCM can range from something as small as 250 mcm up to 2000 mcm.

Another Answer

The abbreviation, 'MCM', stands for 'thousand circular mils'. A 'circular mil' is a North-American method of measuring the cross-sectional area of a circular-section conductor (Europeans use square millimetres for conductors of anyshape).

A 'circular mil' is obtained by squaring the diameter of a circular-section conductor, expressed in mils. A 'mil' is one-thousandth of an inch. As the constant, 'pi', isn't taken into account, it should be obvious that a circular mil is, therefore, a figure representing a cross-sectional area, rather than a true measure of that area.

If necessary, in order to obtain a true cross-sectional area, circular mils can be converted into square mils.

User Avatar

Wiki User

9y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What is mcm wire?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Engineering

Convert 350 mcm to AWG?

There is no defined AWG for 350 MCM. The American Wire Gauge stops at 0000 (4/0), and 350 MCM is bigger than this. An approximate conversion would be 6/0, if there were such a thing. Extrapolating out from 4/0, 6/0 is 334.8 MCM, and 7/0 is 422.2 MCM. These wire sizes don't exist of course, and don't exactly match 350 MCM anyway.


What is the amperage rating of 500 MCM copper conductor?

It depends on a lot of factors. Generally speaking, if the insulation is THHN then the rating is 350 amps. If the insulation is THWN then the rating is 310 amps. The ampere rating for wire depends on the temperature of the environment it will be used in, the insulation rating and the number of circuits installed in a conduit. There are also other factors to consider... like voltage drop in long runs.


How much current does 300 sq mm cable carry?

A 228 sq mm conductor equates to 450 MCM. A conductor of 450 MCM is not a standard AWG wire size. A standard 400 MCM will carry 380 amps. A standard 500 MCM will carry 430 amps. Difference between 400 and 500 MCM amperage's is 50 amps. Transposing between the two amperage's of 50 amps will be 380 + 25 = 405 or 430 - 25 = 405 amps. This is a very rough calculated answer for the question.


Current-carrying capacity of 1000 mcm 5kv rated wire?

The UK wire tables for 1.0 mm2 three-core domestic cable (live/neutral/earth) specify a limit of 10 amps.


Amps on a 600 mcm copper?

475 amps, per NEC 310-16. Note that this is a maximum; there are many reasons to derate the current carrying capacity of the wire.

Related questions

Convert 262 mcm to AWG?

Using the AWG for wire sizes only goes up to 4/0. After that the increases use MCM to size the wire. So your 262 MCM wire size will be same in AWG. There is no 262 MCM in the North American market place. It goes in 50 MCM increments starting at 250 MCM , 300 MCM, 350 MCM, 400 MCM right up to 2000 MCM cable.


What does 750 mcm wire weight?

750 MCM (61 strands) 2.316#/ft 750 MCM (7448 strands) 2.719#/ft


How big around is copper wire mcm 750?

The diameter of an insulated 750 MCM copper wire is 1.25 inches. The insulated 750 MCM copper wiring has 61 strands and has a weight of 2.7 pounds per foot.


What is the weight of 400 mcm copper wire per foot?

500mcm 37 strand copper wire = 1.544lbs/ft.


Convert 350 mcm to AWG?

There is no defined AWG for 350 MCM. The American Wire Gauge stops at 0000 (4/0), and 350 MCM is bigger than this. An approximate conversion would be 6/0, if there were such a thing. Extrapolating out from 4/0, 6/0 is 334.8 MCM, and 7/0 is 422.2 MCM. These wire sizes don't exist of course, and don't exactly match 350 MCM anyway.


What is the amperage rating of 800 MCM Copper wire?

600amps


What is the weight of 3-0 copper wire per foot?

what is the weight of 300 MCM Copper wire


How much does 140 foot of 300 mcm weigh?

A 1000 feet of 300 MCM wire weighs 1021 pounds. It is easy to calculate from there.


What size of copper do you need for a 1250 amps rating?

There are different combination to obtain a current capacity of 1250 amps. A parallel run of #1250 MCM wires. A triple run of #600 MCM wire. The most flexible run would be with a quad run of #350 MCM wire.


What size wire is needed for 1600 amp service?

4 sets of 750 mcm aluminum. Or four parallel runs of 600 MCM copper.


400 amp service what size wire?

A 750 MCM wire with an insulation factor of 90 degrees C is rated at 500 amps. De rated to 80% will allow 400 amps on the wire. A 900 MCM wire with an insulation factor of 75 degrees C is rated at 520 amps. A 1500 MCM wire with an insulation factor of 60 degrees C is rated at 520 amps. Parallel 250 MCM will give you the same usage. A 250 MCM wire with an insulation factor of 75 or 90 degrees C are rated at 255 and 265 respectively. 255 x 2 = 510 x 80% = 408 amps. 265 x 2 = 530 x 80% = 424 amps.


What size conduit for 3 500 mcm wires?

The required size of a conduit raceway for a 3-5000 mcm wire is 300 kcmil. It maximizes the limits on the wire fill for raceways.