Best Answer

first calculate the full load amps of the motor by using formula,

line amps = KW * 1000 / (line volts*1.732*P.F)

Of the mentioned motor the amps will be 96 amps at the P.F 0.8. The motor will have star delta starter so the cable size would be 2 runs of 3c x 70 sq mm AL if laid in air.

User Avatar

Wiki User

13y ago
This answer is:
User Avatar
More answers
User Avatar

Wiki User

12y ago

For an Induction motor, it is recommended that the cable size should be able to bear high motor starting current. For a 75KW, the motor should be run with a special control method: an auto transformer method or Star/Delta method so as to reduce the earlier mentioned high starting current.

Working with a star/delta control method, the motor starts in Star and Runs in Delta.

Star arrangement delivers about 58% of the motor voltage and allows line current to pass into the coils of the motor so that you will require 2x50mm square copper cables per phase to power a 75KW induction motor.

This answer is:
User Avatar

User Avatar

Wiki User

12y ago

It depends on the type of conductor, the configuration of the cores, the type of insulation, the method of installation, and whether or not the cable is armoured! Work out the load current, remembering the 0.75 kW is the output power, not the input power, power! And then check out the Tables in BS 7671:2008Requirements for Electrical Installations.

This answer is:
User Avatar

User Avatar

Wiki User

12y ago

electric cable for 112KW MOTOR 3 phase 385volts 50 hz at 2900 rpm

This answer is:
User Avatar

User Avatar

Wiki User

12y ago

this motor almost draws 198 amps at 0.8 pf

so 150sqmm Al cable or 135 sqmm Copper cable are recommended

This answer is:
User Avatar

User Avatar

Wiki User

9y ago

The current can be estimated at 120 amps, for which the cable size for a short run like 10m is 35 mm-sqd.

This answer is:
User Avatar

User Avatar

Wiki User

12y ago

A 1/0 MCM copper conductor will limit the voltage drop to 1% or less when supplying 129 amps for 33 feet on a 415 volt system.

This answer is:
User Avatar

User Avatar

Wiki User

12y ago

4 x 25 mm2 cable

This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What is cable size for 3 110kw 3 phase induction motor 100 meter run for cable 400v?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

What is the cable size for 1.5KW 3 phase induction motor?

Sir, what is the cable size for 1.5kw 3phase induction motor 400v?


What is the cable size for a 15kw 3 phase induction motor 90 meter runfor cable 400v?

If I consider power factor is 0.85 & motor efficiency is 95% then you have required 4 sq mm wire which is able allow passing 25.47 A current trough it.


Which size cable use for 37 kw induction motor?

To answer this question the voltage of the motor must be stated.


What size contactor required for 110kw 415v star delta start motor?

240 or 415


Does induction motor works on Electromagnetic induction?

Yes the Induction motor works on Electromagnetic induction principle.


Can DOL starter use for 50kw motor?

The answer is yes. I had seen 110kW pump start on DOL starter


What is induction motor?

Induction motor is an AC electric motor which uses electromagnetic induction to induce the electric current in the rotor to produce torque.


Cable size for 25kw motor 100 meter length?

16 mm square


Applications of induction motor?

A single phase induction motor is mainly used in fans.It is capacitor start capacitor run induction motor.In three phase induction motor squirrel cage induction motor is mainly used in elevators,lifts,cranes.slip ring induction motor is mainly used in electrically driven ships.


What is a decripition of Nikola Tesla induction electric motor?

AC Induction Motor


Difference between transformer and induction motor?

1. Induction Motor has an air-gap but transformer has no air gap rather it is mutually link. 2. Induction Motor has high no-load current than transformer. 3. Induction Motor is a dynamic device. 4. Induction Motor has high power factor.


Can a Squirrel Cage Induction motor can be converted to Slip Ring Induction Motor?

yes