In the United States, 208v can be either. It is generally the voltage supplied by a 120/208v 3 phase system. However, using 2 legs of this 3 phase system is called single phase. I won't go into the reasons for that but just understand that 208v can be either single phase or 3 phase.
Yes, but the motor's horsepower rating will not be reached.
No, you will not obtain 230 volts. From a wye connected three phase 480 volt supply, 277 volts can be obtained from one phase leg and the neutral on the wye connection. 480 volts/1.73 (sq. root of 3) = 277 volts.
Only if you want to damage it. "277" Volt 3-phase will usually mean 277 from each phase to neutral, and 480 from phase to phase. By "230 3-phase", you likely mean 120 phase-to-neutral, and 208 phase-to-phase. If you really mean 230, then you are probably NOT talking about a three phase motor.
you need a step up transformer
A 400/230-V three-phase generator hase three line terminals, together with a neutral terminal. The line voltage (i.e. the voltage between any pair of line terminals) is 400 V, while the phase voltage (i.e. the voltage between any line terminal and the neutral terminal) is 230 V.
A 208/230 volt single phase appliance requires a dedicated electrical circuit with a voltage of 208 to 230 volts and a single phase power supply. The appliance should be connected to a properly rated outlet or wiring to ensure safe and efficient operation.
Yes, but the motor's horsepower rating will not be reached.
Outlet for standard electronics is 230 Volt , 50HzThe master feed into Swedish houses is 400 Volt three-phase , 50Hz.When 400 Volt three-phase is split in three single phases it becomes threesingle 230 VoltBigger appliances , e.g Washing-machines, dryers, stoves, used to be400 Volt three-phase, but nowadays most washing-machines and dryersare built for 230 Volt single-phase.
Because its designed to operate at 230-460, not 120-208.
4 tons
A source of 208 volts can be obtained from any two legs of a three phase four wire 208 volt system. The two legs are classed as single phase 208 volts. The lead tags can be L1-L2, L2-L3, or L3-L1 all of which will give you 208 volts. Any of these lead tags to the grounded star point (wye) will give you 120 volts.
The equipment requires a voltage of either 208 or 230 volts.
You can use a transformer to step down the voltage from 400 volts three phase to 230 volts single phase. Connect one of the phases and the neutral of the three phase supply to the transformer primary winding and then connect the secondary winding to get the desired 230 volts single phase supply.
60 Hertz is the frequency that the welder should be connected to, to work as it is designed to.
For a 208 volt single phase motor that pulls 1.4 amps, you would typically use a 2 amp breaker for proper protection. This allows for a small safety margin above the motor's operating current to prevent nuisance tripping. Be sure to consult the motor's manufacturer specifications for the most accurate breaker size.
No, you will not obtain 230 volts. From a wye connected three phase 480 volt supply, 277 volts can be obtained from one phase leg and the neutral on the wye connection. 480 volts/1.73 (sq. root of 3) = 277 volts.
Only if you want to damage it. "277" Volt 3-phase will usually mean 277 from each phase to neutral, and 480 from phase to phase. By "230 3-phase", you likely mean 120 phase-to-neutral, and 208 phase-to-phase. If you really mean 230, then you are probably NOT talking about a three phase motor.