You're right to say that but ONLY (a) if the iron's earth wire was properly connected to the safety earth or ground pin in its plug AND (b) if the socket outlet's earth or ground connector was actually connected to earth or ground.

If the iron's earth or ground wire was actually earthed/grounded the user would not have been able to feel any shock because the fault current would have gone straight to the safety earth /ground wire. No current could have gone through the person holding the iron because, in effect, the earth or ground wire "shunts out" the iron holder's body.

The easy way to be sure of exactly what happened is to find out (a) if the branch circuit's breaker had actually tripped or not, and, if not, then ( b) if only the GFCI or RCD had tripped, if one was fitted...

If if only the GFCI or RCD had tripped, then the person who experienced that shock definitely needs to check that:

(i) the iron's safety earth/ground wire is actually connected to the earth/ground pin of the plug on the end of its cord

and

(ii) that the safety earth/ground wire from the main breaker box is actually connected to the socket outlet's earth or ground connector.

Even doing all that may not be enough: I once repaired a friend's iron that had been dropped (a common way of damaging an iron) and its earth/ground wire had become detached from the earth/ground terminal inside the iron itself. I first found that out by using a test meter to check continuity from the plug's earth/ground pin to the iron's sole plate and there was no connection. I opened-up the iron's casing and found that the brass connector strip that went from the iron's earth/ground terminal to the sole plate had fractured at a sharp bend that had been made in the connector strip when it was manufactured (Not a good design at all!).

One of my bosses when I was an apprentice often used to say "Anyone who says repairing electrical faults is dead easy will probably end up dead much earlier than he expected!"

Some more information:

Appliances such as electric kettles and irons have a hard life because they produce water vapour and steam and often get dropped by careless users. Such conditions may cause the insulation of the wires inside the appliance to "perish" i.e. to become cracked and non-insulating - particularly if it was a low-cost appliance using poor quality insulated wire - and any dampness can then cause a "hot" wire to short either to the neutral wire or to the earth/ground wire, or to both.

The fact the breaker tripped means either

* that it was a bad enough short to raise the current above the branch circuit breaker's tripping point

or

* there was a RCD (also known as a GFCI) in the circuit and that detected an imbalance in current of a few milliamps between the live and neutral wires because of the leak of current to the user's body which was the cause of the shock he received.

<><><>

RCDs (also known as GFCIs) are mandatory for all new installations in Europe nowadays. They first came out about 20/25 years ago and in Europe they used to be fitted to the whole electrical system in a home - lights as well as ring main sockets - but that meant everything went off if something like a kettle or an iron had a short.

Whilst each circuit still has its own circuit breaker - including the lighting circuits - nowadays the wiring regulations say to fit an RCD in the main breaker box/consumer unit to protect only the power sockets on the ring main and also any extra branch circuits in the kitchen, such as for the oven. So the lights should still stay on if the RCD trips because of things like that iron getting an earth/ground fault

If someone doesn't yet have an RCD or GFCI protecting all his power sockets, it would be standard "best advice today" to recommend him to have one fitted.

<><><>

As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.

Before you do any work yourself,

on electrical circuits, equipment or appliances,

always use a test meter to ensure the circuit is, in fact, de-energized.

IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB

SAFELY AND COMPETENTLY

REFER THIS WORK TO QUALIFIED PROFESSIONALS.

User Avatar

Wiki User

14y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What could be the reason a friend had a shock from an iron before the breaker tripped as I was always under the impression that you should not feel anything when a breaker trips?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

What would be the artistic meaning of a first impression?

A first impression is how anything is judged the very first time it is seen. Once that impression is given, it can never be taken back, so it is always important to make the very first impression the best one.


What to do if outlets don't work?

Check for a tripped GFCI (Ground Fault Circuit Interruptor), a blown fuse or a tripped circuit breaker.As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.Before you do any work yourself,on electrical circuits, equipment or appliances,always use a test meter to ensure the circuit is, in fact, de-energized.IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOBSAFELY AND COMPETENTLYREFER THIS WORK TO QUALIFIED PROFESSIONALS.


How to make good impression on my parents?

Be respectful, polite and caring but above all be yourself. A parents love is always there regardless of anything that may have happened.


Screw driver accidentally touched ground wire while screwing a hot black wire in the light switch box. The power went out but the circuit breaker did not trip. Can you tell me how to fix it?

If you didn't burn the wire off then the breaker did trip. Sometimes a tripped breaker is hard to see. Go down the whole panel switching each individual breaker off and then on again. This should rectify the problem. A word from the wise, I have been an electrician for 42 years and always shut the power off before working on equipment.


Outlet stopped working and it is not a GFCI?

First, check the circuit breakers; make sure they are all ON. Find out if any other outlets on the same breaker are working; it's always possible that a breaker is faulty. If the breaker is on and everything else on the circuit is working, it could be as simple as a poor connection inside the outlet. Also even though the outlet is not a GFCI, it may be fed from a GFCI outlet. Check near by outlets to see if any are GFCI and are tripped.


Should the ac breaker and furnace breaker always be on?

Unless you want the power off or there is an overload condition that caused the breaker to trip.


Ceiling fan quit working no power at switch circuit breaker not tripped?

I have seen cases where an open breaker is the cause of such problems. It appears to be on, but is open internally. Check the voltage with a meter or temporarily piggy-back the fan circuit on another breaker. If it isn't the breaker it is a connection somewhere in the circuit leading to the fan switch. If the power is coming from a GFCI outlet, check that. Otherwise, you start at the breaker measuring voltage and then try and find other spots in the circuit before the fan switch and check voltages there. You can also go a bit high tech and buy a signal tracer for about $30 and check out the circuit wiring. Then there is always an electrician who will likely find the problem quickly.


Can a 220 VAC breaker be single pole or does it have to always be a double pole breaker?

U.S. 240 VAC breakers are always double pole since they are protecting two legs of the circuit.


How do you fix a panel's circuit breaker when it tripped?

As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.Before you do any work yourself,on electrical circuits, equipment or appliances,always use a test meter to ensure the circuit is, in fact, de-energized.IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOBSAFELY AND COMPETENTLYREFER THIS WORK TO QUALIFIED PROFESSIONALS.


What is the helping verb in the sentence He must have tripped on a rock?

must - is called a modal auxiliary verb, must always goes before a main verb in this sentence the main verb is tripped. have - is an auxiliary verb in this sentence. Both of these can be called helping verbs


Is there any disadvantage of selecting over rated circuit breaker?

If i understand you correctly, yes there certainly can be. If you replace, say a 10 amp breaker with a 20 amp. you are losing the safety factor - the whole purpose of the breaker to begin with. Always replace a breaker with the exact same amperage rating!


What is a situation where you think it is especially important to make a positive first impression?

Whenever you meet a person you do not know, it is VERY important that you give them a good impression. Remember, ALWAYS be yourself !