A grounded neutral will be at earth potential. A floating neutral will be at a voltage dependent upon the voltage imbalance between phases, and the design of the transformer.

User Avatar

Wiki User

14y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Voltage across Neutral and earth for a 3 phase auto transformer?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Engineering

How do you earth in the 1600 kva transformer?

In 1600 kva transformer we provide NGR (Neutral grounding resistance)


What is maximum distance of Earth pit for transformer neutral earthing?

100meter


What is the reason for using a neutral current transformer on a transformer?

A current transformer is primarily used at the neutral point of a transformer for earth fault protection. A neutral current transformer will measure any ground fault current which will essentially flow from the star point of the transformer. A fault-detection device other devices is connected to the current transformer and, if the fault current exceeds a certain trigger value, the fault-detection device will give a trip command to an earth-fault relay to disconnect the supply of electricity to the transformer.


Do all electrical power sources flow to earth e.g. Secondary winding of an isolating transformer with no earth connection on the neutral line?

There are situations where the secondary of a transformer is not grounded and the neutral is not connected to the neutral of the primary. This can cause a potential shock hazard so the secondary side needs to be protected.


How do you reduce neutral to earth voltage below 5volts as it is showing 9 volts at my PC powersocket?

First you have to check and conform there is no earth leakage in your home. Then conform the earth is perfect. then check the P-N , P-E and N-E voltage. If the P-N voltage is less than that of P-E voltage, problem is IMPROPER NEUTRAL of your supply system.Means,you have to balance the load of the supply system or conform the neutral earthing in distribution transformer side by the help of Electricity board authority. If the P-E voltage is less than that of P-N voltage , you have to strengthen your earth. After that all above mention, you will get P-N V is almost equal to P-E V and N-E V will come around 0-3 V.

Related questions

Why there is zero volt across neutral earth of isolation transformer?

Geez, because it is just that; A NEUTRAL EARTH, there should be equal potential on each side, therefore no current flow, and no voltage.


How do you reduce neutral and earth voltage up to 0 volts?

If you are reading a voltage it is the drop across the resistance to ground. To get rid of the voltage get the resistance lower. This can be accomplished by installing more ground rods to the grounding system. Utility companies usually like 3 ohms to ground or less.


How do you reduce neutral to earth voltage in three phase system?

It is done by connecting the neutral to earth at the transformer that produces the three-phase supply. If the three phase wire supply equal currents, there is no current in the neutral wire and its whole length stays at earth potential, but if there is current in the neutral it produces a small voltage on the neutral at places away from the transformer.


What is an Earthed voltage transformer?

An earthing transformer provides a neutral in a delta connected system.


How do you calculation of selecting Neutral Earthing Transformer?

iT IS ISMILAR TO THE GROUND RESITOR CALCULATION FOR TRANSFOMER THE TYPICAL EXAMPLE WAS ANSWERED EARLIER FOR TRANSFORMER DT.19-06-2009 Neutral of transformer can be grounded solidly earthed OR with Neutral Grounded with Resistance. Typical shunt calculations fro 5 MAV 11/6.6 kv transformer neutral are as :_ Transformer rating = 5 MVA Voltage ratio = 11/6.6 KV Vector Group = Dyn11 (6.6 KV ground through Resistor) During Earth fault voltage between Neutral & Earth = 6.6/√3 = 3.81 KV Earth Fault current will be limited to = 5 x 10³ /(√3 x 6.6) = 437.38Amp. N.G.R. value in ohm = V / I = (3.81 x 10³) / 437.38 = 8.71 Ohm Value of N.G.R. is 437.38 Amp, 8.71 Ohm., 10 Sec NGR are inserted On Higher voltage to restrict earth fault current BY SRI


How do you earth in the 1600 kva transformer?

In 1600 kva transformer we provide NGR (Neutral grounding resistance)


How is the neutral point in a star connection created?

In a distribution transformer's star-connected secondary, the common point of connection is called the 'star point' and is connected to earth. The star point then provides the neutral connection for the transformer secondary, providing a return path for any unbalanced currents due to an unbalanced three-phase load.This arrangement provides a four-wire distribution system, comprising three line conductors and one neutral conductor (in addition, there are various methods of providing an earth connection to consumers). The line-to-line voltage is called a line voltage (in the UK, 400 V), while a line-to-neutral voltage is called a phase voltage (in the UK, 230 V). The line voltage being 1.732 x phase voltage.


What is maximum distance of Earth pit for transformer neutral earthing?

100meter


What is the reason for using a neutral current transformer on a transformer?

A current transformer is primarily used at the neutral point of a transformer for earth fault protection. A neutral current transformer will measure any ground fault current which will essentially flow from the star point of the transformer. A fault-detection device other devices is connected to the current transformer and, if the fault current exceeds a certain trigger value, the fault-detection device will give a trip command to an earth-fault relay to disconnect the supply of electricity to the transformer.


Do all electrical power sources flow to earth e.g. Secondary winding of an isolating transformer with no earth connection on the neutral line?

There are situations where the secondary of a transformer is not grounded and the neutral is not connected to the neutral of the primary. This can cause a potential shock hazard so the secondary side needs to be protected.


Why need neutral eathing in transformer and generator?

In the case of a step-down transformer, the secondary winding is earthed (grounded) to provide protection against an insulation breakdown between the high voltage and low voltage windings -in other words to deliberately cause an earth fault that will initiate the operation of the high-voltage system's protection system. At the same time, it provides a zero-potential point of reference for all potentials measured on the low-voltage system, and a means by which earth-fault currents can return to the source. In the case of a three-phase transformer supplying an unbalanced load, an unearthed star-point will result in a 'floating neutral', which means that the three phase voltages will likely be unbalanced (i.e. different from each other).


What is the total of a phase to earth voltage on 11000 volts?

An 11,000 volt three-phase supply has a voltage of 6351 from live to neutral, when there is a neutral wire.